10751

Addressable fire alarm control panel BP-FD-ACP300-1L

The single loop 32 zone fire alarm control panel offers the following features:

  • Up to 324 addresses on one loop
  • An easy to read, 4.3’’ color screen LCD with a resolution of 480×272
  • Zone indication and control panel (ZCP) for 32 zones gives a quick indication of the location of an alarm
  • Record capacity of 1000 historical events for each of historical fire, historical fault and historical operation
  • An independently programmable conventional sounder circuit output
  • Integral power supply and battery
  • Integral printer
  • Flexible and intuitive cause and effect programming on front panel
  • Zone test, point test and module start/stop testing facilitate the commissioning
  • U-disk interface makes the load and save of configuration or historical data convenient for system commissioning and maintenance
  • Hierarchy management with three access levels
  • Anti-tamper protection by a key lock
  • CAN bus for interconnection of up to 20 FACPs and RS-485 for connection with up to 30 fire indicating panels per FACP
Buy now!

Specifications

Technical specification
Model: BP-FD-ACP300-1L
Power Supply
Mains supply 230VAC (-15%, +10%). 47 ~ 63Hz. Max current 0.8A
Mains fuse T3.15AL250V
Operating voltage 18.5 ~ 30VDC
Recommended mains cable Screened or standard/black mains cable, cable size 0.75mm2
Power rating Imax.a=1.2A; Imax.b=2.6A; Imin=0.65A
Max. charging current 1.2A
Max. battery supply current 4A (when the Mains is disconnected)
Battery capacity, type and

recommended model

Max. capacity 2×12V/17Ah; Min. capacity 2×12V/12Ah

VRLA. PS-12170 for 17Ah (Power-sonic), PS12120 for 12Ah (Power-sonic)

Max. internal resistance of battery 1.5Ω
Battery fuse F8AL250V
Recommended battery cable 14AWG
Quiescent current (full loaded) < 0.4A
Outputs
S.C. Out (+, -) Output voltage 18.5 ~ 30VDC
Max. output current 0.5A
Fuse rating F1AL250V
End of line resistor 4K7
Recommended type of cable Plain unscreened cable, 1.5mm2
Cable diameter 1mm2 ~ 2mm2
Transmission distance ≤1500m
Max. number of sounders @50mA 20
F.P.E. Out (+, -)

F.A. Out (+, -)

Output voltage 18.5 ~ 30VDC
Max. output current 0.5A
Fuse rating F1AL250V
End of line resistor 4K7
Recommended type of cable Plain unscreened cable, 1.5mm2
Cable diameter 1mm2 ~ 2mm2
Transmission distance ≤1500m
Fault Out

(NC, COM, NO)

Contact capacity 30VDC@2A, 125VAC@0.5A
Recommended type of cable Plain unscreened cable, 1.5mm2
Cable diameter 1mm2 ~ 2mm2
24VK (+, -) Output voltage 18.5 ~ 30VDC
Max. output current 0.6A
Fuse rating F1AL250V
Recommended type of cable Plain unscreened cable, 1.5mm2
Cable diameter 1mm2 ~ 2mm2
Input
Class change (+, -) Input mode Passive
Cable resistance ≤500Ω
Recommended type of cable Plain unscreened cable, 1.5mm2
Cable diameter 1mm2 ~ 2mm2
Loop
Loop Out (+, -)

Loop In (+, -)

Output voltage 16.5 ~ 30VDC, pulse
Output current 0 ~ 0.3A
Loop type Class A
Recommended type of cable Screened or unscreened twisted-pair, 1.5mm2
Transmission distance ≤1000m
Cable diameter 1mm2 ~ 2mm2
Network communication
RS-485 Max. number of FIPs 30
Transmission rate 9600 bps
Recommended type of cable Screened or unscreened twisted-pair, 1mm2
Transmission distance ≤1000m
Cable diameter 1mm2 ~ 5mm2
CAN Max. number of panels 20
Transmission rate Optional: 10K, 20K, 50K and 100K bps
Recommended type of cable Screened or unscreened twisted-pair, 1mm2
Transmission distance ≤1000m
Cable diameter 1mm2 ~ 5mm2
Physical dimensions
Approx. Dimensions of the panel (W×H×D) 430×560×170mm
Approx. weight (without battery) 14kg
Operating conditions
Temperature range: 0°C~ 45°C; Max relative humidity: 95% (40°C ± 2°C, no condensation)