10771

Addressable heat detector BP-FD-AHD302

  • It can realize electronic coding and rewrite the address via coder in situ.
  • Within a single-chip microcomputer, it can realize real-time data acquisition and processing, realize a curve tracing for the field situation.
  • It has a temperature compensation function and a sensor fault detection function (fault reporting to fire alarm control panel).
  • Non-polarity, two-bus connection that ensures convenient installation and maintenance.
  • Designed with an upper cover and a lower cover and installed on an independent base, it can be installed, debugged and maintained conveniently.
  • Built-in remote indicator output terminal, drive remote indicator lit when fire alarm
Buy now!

Specifications

Technical specification
Model: BP-FD-AHD302
Technical Parameters
Operating Voltage Loop 24V (18V ~ 28V)
Standby Current <0.3mA
Alarm Current <1.5mA (without remote indicator)

<3.5mA (with remote indicator

Class A2
Fire LED Red, Flash in polling, and illuminate in alarming
Remote indicator output Polarity-sensitive output, directly connect to remote indicator (built in 10k resistor in series, max. output current is 2mA); The red indicator will blink in the monitoring status or remain lit in the alarm status.
Programming Electronically addressed
Programming Range Occupying one address within 1 ~ 324
Wiring Loop: two wire, polarity-insensitive
Environmental Temperature -10℃ ~ +50℃
Relative Humidity ≤95%, non-condensing
Material of Enclosure ABS
Dimension Diameter: 100mm

Height: 60mm (with the base)

Mounting Hole Distance 44.5mm ~ 64.3mm
Weight About 115g (with the base)