Model: BP-FD-CCP100 |
Power specification |
Mains supply voltage |
110VAC or 220VAC |
Internal power supply |
27.2VDC |
Total output current limited |
500mA@240VAC |
Main supply monitor for fault |
YES |
Battery protection for low voltage |
YES |
Batteries (default configuration) |
12V2.3AH*2 |
Detector circuit specification |
Number of circuits |
1 |
Line fault monitor for open circuit |
YES |
Line fault monitor for short circuit |
YES |
Line fault monitor for detector removal |
Yes, if end of line monitor unit fitted in place of end of line resistor |
End of line device |
6.8kΩ, 5% tolerance, 0.5-1W (color code – blue, grey, red, gold) |
Detector continuity diodes |
Silicon 1N4001or Schottky type (required if end of line monitor unit fitted to give detector removal fault) |
Call point resistor value |
470 to 680Ω, 0.5 or 1 watt |
Maximum number of smoke/heat detectors per zone |
20 (based on a total detector current of 2mA, each detector consuming 100μA). Note: if end of line monitor unit is fitted, for correct operation maximum voltage drop must not exceed 12 volts |
Maximum number of manual call points per zone |
No limit |
Sounder circuit specification |
Number of general circuits |
2 |
End of line resistor value |
6.8kΩ, 5% tolerance, 0.5-1W (color code – blue, grey, red, gold) |
Line fault monitor for open circuit |
Yes |
Line fault monitor for short circuit |
Yes |
Outputs fused AT |
600mA |
Maximum number of bells @50mA of each Sounder output |
12 |
Fuses |
Battery fuse |
1.85A resettable fuse |
Sounder outputs |
400mA F 20mm |
Fire output |
Output type |
NC and NO relay |
Maximum current |
100mA |
Connection block |
Largest acceptable conductor size |
2.5mm2 |
Smallest acceptable conductor size |
0.75mm2 |
Size and weight |
Dimensions (mm) |
272 x 200 x 70 |
Weight (with batteries) |
5.5kg |