Conventional fire alarm control panel BP-FD-CCP400

  • It has 2 level control mode by a lock
  • It has 24VDC power supply output
  • It has FIRE and FAULT signal output
  • It has 2 general sounders output
  • Each zone has 1 circuit detectors input
  • Each zone can be disable by a button
  • It has RESET button to reset the panel
  • It has SILENCE button to stop BUZZER and SOUNDERS
  • It has EVACUATE button to start a manual fire alarm immediately
  • It has an optional GSM module for fire alarm by SMS
  • It is economic, user-friendly and easy maintenance
Buy now!

Specifications

Technical specification
Model: BP-FD-CCP400
Power specification
Mains supply voltage 110VAC or 220VAC
Internal power supply 27.2VDC
Total output current limited 3A@220VAC
Main supply monitor for fault YES
Battery protection for low voltage YES
Batteries (default configuration) 12V2.3AH*2
Detector circuit specification
Number of circuits 4
Line fault monitor for open circuit YES
Line fault monitor for short circuit YES
Line fault monitor for detector removal Yes, if end of line monitor unit fitted in place of end of line resistor
End of line device 6.8kΩ, 5% tolerance, 0.5-1W (color code – blue, grey, red, gold)
Detector continuity diodes Silicon 1N4001or Schottky type (required if end of line monitor unit fitted to give detector removal fault)
Call point resistor value 470 to 680Ω, 0.5 or 1 watt
Maximum number of smoke/heat detectors per zone 20 (based on a total detector current of 2mA, each detector consuming 100μA). Note: if end of line monitor unit is fitted, for correct operation maximum voltage drop must not exceed 12 volts
Maximum number of manual call points per zone No limit
Sounder circuit specification
Number of general circuits 2
End of line resistor value 6.8kΩ, 5% tolerance, 0.5-1W (color code – blue, grey, red, gold)
Line fault monitor for open circuit Yes
Line fault monitor for short circuit Yes
Outputs fused AT 600mA
Maximum number of bells @50mA of each Sounder output 12
Fuses
Battery fuse 1.85A resettable fuse
Sounder outputs 600mA resettable fuse
Fire output
Output type NC and NO relay
Maximum current 100mA
Connection block
Largest acceptable conductor size 2.5mm2
Smallest acceptable conductor size 0.75mm2
Size and weight
Dimensions (mm) 315 x 250 x 90
Weight (with batteries) 7kg